27 Nisan 2008 Pazar

ASPERA Commercial Hermetic Compressors

Medium/High Back-Pressure Models R134a (Rated at -5°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1/6 326 6.05 RSIR 6 4.9 1.5 11.5 2339004 2316021
1/4 443 8.78 CSIR 8 6 2.1 11.0 2278018 2319011
1/3 637 12.12 CSIR 8 6 2.5 13.8 2283002 2321032
3/8 835 17.4 CSIR 8 6 3.9 20.0 2283011 2285143
1/2 1003 20.4 CSIR 8 6 4.9 21.0 2277034 292149
3/4 1471 26.2 CSIR 9.6 8 5.7 35.0 2302002 2289006
1 1764 34.4 CSR 9.6 8 6.0 31.0 1253012 2291007

Medium/High Back-Pressure Models R22 (Rated at -5°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1/6 339 4.52 CSIR 8 6 1.9 15.3 2278011 2319013
1/5 394 5.02 CSIR 8 6 2.1 15.3 2278011 2316019
1/4 485 6.05 CSIR 8 6 2.6 13.8 2278018 2316018
1/3 561 7.28 CSIR 8 6 2.8 16.5

3/8 670 8.78 CSIR 8 6 3.1 13.8 2278018 2316018
1/2 980 12.12 CSR 8 6 3.1 16.1 1253009 2321042
5/8 1073 14.5 CSR 9.6 6 3.4 18.0 2283038 2285072
3/4 1345 17.4 CSR 9.6 6 4.5 20.0 1253009 Internal
1 1919 23.8 CSR 9.6 6 5.8 30.0 1253003 2291007
1 1/4 2159 26.2 CSR 12.8 8 6.7 33.7 1253008 2289005
1 1/2 2842 34.4 CSR 12.8 8 9.8 50.0 1253014 2295001
2
42.75 3PH





2.5
57.68 3PH





3
66.34 3PH





3.5
72.61 3PH





4
90.96 3PH





5
101.13 3PH





Medium/High Back-Pressure Models R507 (Rated at -5°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1/6 375 4.52 CSIR 8 6
15.3 2278011 2316020
1/5 437 5.02 CSIR 8 6
15.3 2283052 2317014
1/4 528 6.05 CSIR 8 6
13.8 2278018 2316018
1/3 585 7.28 CSIR 8 6
16.5 2283002 2317020
3/8 721 8.78 CSIR 8 6
13.8 2283002 2321032
1/2 1080 12.12 CSR 8 6
14.1 1253023 2321045
5/8 1220 14.5 CSIR 9.6 6
22.0 2283038 2285072
3/4 1471 17.4 CSR 9.6 6
26.5 1253014 2291036
1 1998 21.7 CSR 9.6 6
27.5 1253009 2289016
1 1/4 2456 26.2 CSR 12.8 8
43.0 1253007 2289003
1 1/2 3014 32.7 CSR 12.8 8
43.0 1253007 2297017

Low Back-Pressure Models R134a (Rated at -23.3°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1/3 96 19.04 CSIR 8 6 2.8 13.0 2283011 2285006
1/2 602 27.12 CSIR 9.6 8 3.0 24.0 2302001 2289011
3/4 815 38.00 CSIR 12.8 8 4.5 35.0 2302002 2289002

Low Back-Pressure Models R507 (Rated at -23.3°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1/3 476 12.12 CSIR 8 6 2.7 16.4 2283032 2317013
3/8 586 14.5 CSIR 9.6 6 3.4 22.0 2277031 2292105
1/2 752 17.4 CSR 9.6 6 2.74 18.0 1253022 Internal
5/8 910 20.4 CSR 9.6 6 3.2 21.0 1253012 Internal
3/4 1125 26.2 CSR 9.6 8 4.0 26.0 1253008 Internal
1 1477 34.4 CSR 12.8 8 5.3 36.0 1253010 internal
2 1861
3PH 19.0 12.7



3 2637 66.34 3PH 19.0 12.7



4 4395 101.13 3PH 19.0 12.7



High Back-Pressure Models R22 (Rated at +7.2°C)

hp Nominal
capacity
(watts)
Disp/ment
(cm3)
Type Compressor
connections
(mm)
Electrical
data
Replacement Relay
and Overload -
BOC Part No.




Suction Disch F.L.A.
(amps)
L.R.A.
(amps)
Relay Overload
1 2878 23 PSC 9.6 6.4 5.8 30.0
-
2291007
1 1/4 3596 26.2 PSC 9.6 8 7.2 37.0
-
2295002
1 1/2 4416 32.7 PSC 12.8 8 10.5 51.0
-
2297001
1 1/2 4838 34.4 PSC 12.8 8 9.8 50.0
-
2295001

1 yorum:

Adsız dedi ki...

Check that the compressor is cycling on and off regularly.
Avoid leaving doors open when entering and leaving cool rooms. Self closing doors are useful, but may not be suitable for all applications. Plastic strip curtains or swinging doors are good options for frequently accessed cool rooms. Automatic doors and those operated by remote control may also be suitable.Refrigeration Equipment